1. Certified to 80 PLUS® Platinum standard, peak efficiency exceeds 94%
2. Supports N+1 redundant configuration, with cold standby and hot-swap functions
3. Equipped with black-box fault recording and online firmware upgrade functions
4. High power factor and low harmonic distortion
5. Standard dimensions: 185×73.5×40mm
| Model HK800B-S1 | Rated Power | 800W(Platinum) | |||
| Input | 90V-264VAC(47Hz-63Hz), 240Vdc | ||||
| Output | Load Range | Voltage | Ripple & Noise | ||
| Min | Max | ||||
| +12V | 1A | 65A | ±5% | ≤120mVp-p | |
| +12VSB | 0.1A | 3A | ±5% | ≤120mVp-p | |
| Support N+1(0≤N≤3) Redundant applications and hot swap | |||||
| Standby Power Consumption | ≤5W | ||||
| Efficiency | 10%load ≥88% | 20%load ≥93% | 50%load ≥94% | 100%load ≥92% | |
| Protective Function | input undervoltage, input overvoltage, input current limiting, output overvoltage, output overcurrent, output short circuit, over temperature protection | ||||
| Working Environment | Air Temperature: 0-55℃, Relative Humidity: 0%-95% no condensation | ||||
| Storage Environment | Air Temperature: -20-70℃, Relative Humidity: 0%-95% | ||||
| EMI | EN55032 class B, GB/T9254 Class B | ||||
| Earth Leakage Current | ≤3.5mA(240VAC/50Hz) | ||||
| MTBF Value | 200,000H | ||||
| Cooling Method | Forced air cooling with fan heat dissipation | ||||
| Package Method | 8pcs/carton | ||||
| Typical Dimensions | 185(L)×73.5(W)×40(H)mm | ||||
| Design Standards | CE, CB, FCC, UL, TUV, LVD, CCC, 80 Plus | ||||
| Application | Network servers, industrial PCs | ||||