1. Certified to 80 PLUS® Titanium standard, efficiency exceeds 96% under 20%–50% load
2. Supports N+1 redundant configuration, featuring cold standby and hot-swap functions
3. Built-in black-box fault log storage and online firmware upgrade functions
4. High power factor with low harmonic distortion
5. Standard dimensions: 185×73.5×40mm
| Model HKS3200D1 | Rated Power | 3200W(Titanium) | |||
| Input | 90~264Vac, 47~63Hz, 240Vdc | ||||
| Output | Load Range | Voltage | Ripple & Noise | ||
| Min | Max | ||||
| +12V(110Vac) | 3A | 119A | ±5% | ≤120mVp-p | |
| +12V(210Vac) | 3A | 246A | ±5% | ≤120mVp-p | |
| +12V(230Vac) | 3A | 262A | ±5% | ≤120mVp-p | |
| +12VSB | 0.1A | 2.1A | ±5% | ≤120mVp-p | |
| Support N+1(0≤N≤3) Redundant applications and hot swap | |||||
| Standby Power Consumption | ≤5W | ||||
| Efficiency | 10%load ≥90% | 20%load ≥96% | 50%load ≥96% | 100%load ≥93.5% | |
| Protective Function | input undervoltage, input overvoltage, input current limiting, output overvoltage, output overcurrent, output short circuit, over temperature protection | ||||
| Working Environment | Air Temperature: 0-55℃, Relative Humidity: 5%-95% no condensation | ||||
| Storage Environment | Air Temperature: -40-70℃, Relative Humidity: 5%-100% | ||||
| EMI | EN55032 Class A | ||||
| Earth Leakage Current | <3.5mA at 240V RMS | ||||
| MTBF Value | 200,000H | ||||
| Cooling Method | forced air cooling | ||||
| Package Method | Outer carton with paper divider inserts | ||||
| Typical Dimensions | 185(L)×73.5(W)×40(H)mm | ||||
| Design Standards | CE, CB, FCC, UL, TUV, LVD, CQC, 80 Plus | ||||
| Application | General, storage & AI servers in data centers | ||||